What Is the Difference Between a Current Transformer and a Voltage Transformer?

Nov 23, 2026

Leave a message

In power systems, directly measuring a high-voltage busbar or a high-current line is extremely dangerous. The role of the current transformer (CT) and the voltage transformer (PT) is to scale high voltage and high current down proportionally into low-voltage, low-current signals for instrument metering and relay protection. Although the two are often collectively referred to as "instrument transformers," they differ fundamentally in wiring method, operating state, and prohibited practices. Selecting the wrong type, wiring them incorrectly, or operating them improperly can lead to inaccurate measurement at best and equipment burnout or even personal injury at worst.

 

This article will elaborate on five dimensions-basic definitions, wiring differences, operational prohibitions, applications, and rated values-to help power industry practitioners, electrical engineers, and procurement personnel quickly grasp the core points.

I. Basic Definitions

The current transformer (CT) core task is to convert the large current on the primary side proportionally into a small current on the secondary side. Structurally, its primary winding has very few turns (usually only one turn or a few turns) with a large conductor cross-section, and it is connected directly in series into the measured line.

Current Transformer-1

 

 

The voltage transformer (PT) is used to step down high voltage proportionally to a standard low voltage. Its structure is similar to an ordinary step-down transformer: the primary winding has many turns and is connected in parallel to the measured busbar or line, and the secondary side outputs a standard voltage signal.

 

voltage transformer

 

 

In short: the CT handles "current," and the PT handles "voltage." Only when the two work together can the power and energy data of the power line be fully reconstructed.

II. Wiring Differences: The Essential Difference Between Series and Parallel Connection

Current transformers use series wiring. Because the current in the line must be measured, the CT's primary winding must carry the full measured current. Since the primary winding has extremely low impedance, series connection does not cause a noticeable voltage drop that would affect normal line operation.

 

Voltage transformers use parallel wiring. The PT only needs to "sense" the busbar voltage and does not require the main current to flow through its interior. Therefore, the primary winding is connected in parallel between phase and ground or between phases, and the secondary side is connected to high-impedance voltmeters or the voltage coils of protection devices.

 

This wiring difference directly determines the different nature of the secondary-side load: the CT secondary side is connected in series with current coils (extremely low impedance), while the PT secondary side is connected in parallel with voltage coils (extremely high impedance).

III. Operating State Differences: The Most Critical "Prohibition" Red Lines

This is the link most easily confused in operation and maintenance and also the most dangerous.

Current transformer: The secondary side must NEVER be open-circuited. During normal operation, the CT secondary circuit is close to a short-circuit state. The magnetic flux generated by the secondary current has a demagnetizing effect on the primary flux, so the total core flux is very low. Once the secondary side opens, the demagnetizing effect disappears, and the entire primary current becomes magnetizing current. The core flux saturates sharply, causing the core to heat severely and burn the insulation, while simultaneously inducing a dangerous voltage of several thousand volts or even higher across the secondary winding terminals, seriously threatening personal and equipment safety. Therefore, fuses or circuit breakers must not be installed in the CT secondary circuit, and the secondary terminals must be shorted with a shorting link before removing instruments.

 

Voltage transformer: The secondary side must NEVER be short-circuited. During normal operation, the PT is close to a no-load state, and the secondary load impedance is very large. If the secondary side short-circuits, since the PT internal impedance is very small, the short-circuit current will increase sharply, burning the secondary winding and even endangering the insulation of the primary system. Therefore, fuses are usually installed on the PT secondary side as short-circuit protection-exactly the opposite of the requirement that fuses must never be installed on a CT.

 

Comparison Item

Current Transformer (CT)

Voltage Transformer (PT)

Secondary operating state

Close to short circuit

Close to no load

Absolutely prohibited

Open circuit

Short circuit

Secondary protective device

Fuses strictly prohibited

Fuses should be installed

Operation before removing meters

Short the secondary terminals first

Disconnect the secondary circuit first

IV. Application Differences: Division of Responsibilities in Metering and Protection

The two overlap in application but have different emphases.

Current transformers are mainly used for: current measurement, electrical energy metering (meter current circuit), overcurrent protection, and differential protection. Because a CT can faithfully reproduce the primary current waveform, protection CTs are further divided into metering class (high accuracy during normal operation, easily saturated during short circuits to protect instruments) and protection class (does not saturate during short circuits, ensuring reliable operation of protection devices).

 

Voltage transformers are mainly used for: busbar voltage monitoring, electrical energy metering (meter voltage circuit), distance protection, and undervoltage load shedding and other relay protection functions. The PT provides voltage amplitude and phase information to protection devices and is an important basis for judging the operating state of the system.

V. Rated Value Differences: Standard Secondary Signals

To make instruments and protection devices standardized and universal, the secondary rated values of instrument transformers are uniformly specified.

Current transformer secondary rated current is usually 5 A or 1 A. The 5 A system is widely used in 10–110 kV distribution systems due to its small size and low cost; the 1 A system has obvious advantages in long-cable circuits or high-voltage substations, where line losses are only 1/25 of those of the 5 A system, greatly reducing the control cable cross-section. Selection should be based on a comprehensive judgment combining cable length and load impedance.

 

Voltage transformer secondary rated voltage is usually 100 V (line voltage), with a phase voltage of 100/√3 V (about 57.7 V). In some applications, 220 V output is also used for power supply or specific control circuits, but the standard signal for metering and protection is mainly 100 V.

VI. Frequently Asked Questions

Q1: Why is "the secondary side must not be open-circuited" specifically marked below the CT nameplate?

A:Because this is the most dangerous operating prohibition for a CT. The ultra-high voltage generated by an open circuit is enough to break down insulation and endanger life, and the nameplate warning is a mandatory safety reminder. O&M personnel should remember: shorting the CT secondary terminals is the first action before removing meters.

 

Q2: A fuse is installed on the PT secondary side-why can't one be installed on a CT?

A:The PT fuse is used to cut off the fault current when the secondary side short-circuits, protecting the PT itself. Once the CT secondary circuit opens (a blown fuse is equivalent to an open circuit), the CT enters the dangerous open-circuit state. Therefore, the CT secondary circuit must remain completely closed, and any series-connected protective device is a hidden hazard.

 

Q3: How should I choose between a 1 A and a 5 A CT?

A: It depends on cable length. If the CT installation point is far from the protection room or metering cabinet (such as in 330 kV and above substations), the secondary circuit cable is long; choosing 1 A can significantly reduce line voltage drop and losses and also reduce the cable cross-section. In 10–110 kV distribution installations, cables are usually short, and 5 A CTs are smaller and cheaper, making them more economical and practical.

VII. Conclusion

The fundamental difference between current transformers and voltage transformers can be summed up in one sentence: CTs are connected in series to measure current, and the secondary side must not be open-circuited; PTs are connected in parallel to measure voltage, and the secondary side must not be short-circuited. Mastering this core principle will help you avoid the vast majority of fatal errors in wiring, commissioning, and operation and maintenance.

 