LWL-126 Outdoor High Voltage AC SF6 Circuit Breaker

LWL-126 Outdoor High Voltage AC SF6 Circuit Breaker

The circuit breaker meets the requirements of GB1984-2003 and IEC62271-100-2001. It uses SF6 gas as insulation and arc extinguishing medium, adopts self-energy arc extinguishing principle, and uses a new type spring operating mechanism, which has the characteristics of strong breaking ability, small operation power and high reliability.
Send Inquiry
Description
Technical Parameters

Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of lwl-126 outdoor high voltage ac sf6 circuit breaker in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium lwl-126 outdoor high voltage ac sf6 circuit breaker made in China here from our factory.

 

Product Description

 

LWL-126 outdoor high-voltage SF6 circuit breaker is suitable for AC 50Hz(60Hz)126kV power system, is the power system control and protection equipment, can also be used as a contact circuit breaker.


The circuit breaker meets the requirements of GB1984-2003 and IEC62271-100-2001. It uses SF6 gas as insulation and arc extinguishing medium, adopts self-energy arc extinguishing principle, and uses a new type spring operating mechanism, which has the characteristics of strong breaking ability, small operation power and high reliability.

 

Product Features

 

1.The circuit breaker adopts three-phase column type single-break structure,and is equipped with a spring-operated mechanism for three-phases, in centered arrangement, three phases linkage transmissed, so the appearance is novel and exquisite.
2. The circuit breaker adopts SF6 gas as insulation and arc extinguishing medium,and the three poles of the circuit breaker are with SF6gas connected during operation, and a pointer density relay is adopted to monitor its pressure and density.
3. Due to the use of self-energy arc extinguishing principle,and the circuit breaker movement system is with optimization design,so it effectively improves the mechanical efficiency,minimize the operating power;
4. The circuit breaker has excellent breaking performance and long electrical endurance life;and with high mechanical reliability and can be operated frequently;
5. The installation base frame and support are made of high-quality steel plate wholy bent,with all adopt hot-dip galvanizing process for the surface treatment.All exposed fasteners are made of high-strength materials and hot-dip galvanized,or use stainless steel spare parts.The outer housing of the mechanism cabinet is made of stainless steel, so the breaker is with excellent anti-corrosion performance;
6. Because of the inherent high insulation strength of SF6 gas,and the circuit breaker adopts the optimal contact movement,so the circuit breaker could break the capacitive current without re-strike;
7. High level of external insulation.The external insulation is in large creepage distance design,with creepage distance ratio≥31mm/kV, and with excellent anti-dirt performance. It could be safe operated in harsh environment;
8. Strong current-carrying capacity: if the breaker has temperature rise test at 1.2 times the rated current 3150A, which is in 3780A,the temperature rise at each point still has a large margin;
9. The overall appearance of the product is in compact structure,convenient for on-site installation and commissioning,and with small maintenance workload.

 

Product Show

 

product-520-520
product-520-520

 

LWL-126 SF6 Circuit Breaker Technical Specification

 

S.N.

Name

Unit

Data

1

Rated voltage

kV

126

2

Insulation Level

1min power frequency withstand voltage (effective value,dry,wet types)

Between factures

kV

230

Between poles or pole to earth

kV

230

Lightening impulse withstand voltage(peak)(full wave1.2/50ps)

Between factures

kV

550

Between poles or pole to earth

kV

550

3

Rated frequency

Hz

50/60

4

Rated current

A

3150

5

Rated short circuit breaking current

kA

40

6

Rated short time withstand current

kA

40

7

Rated peak withstand current

kA

100

8

Rated short circuit endurance

s

3

9

Rated short circuit making current peak

kA

100

10

Short–line fault breaking current

kA

36/30

11

Rated cable line charging breaking current

A

31.5

12

Rated out–of–synchronism breaking current

kA

10

13

Total breaking operations at rated short circuit breaking current

cycle

20

14

First–pole–to–clear factor

 

1.5

15

SF6 gas pressure (20℃)

Mpa

0.5

16

Rated voltage of control and auxiliary circuits power

 

DC220V DC110V

17

Rated operation sequence

 

O–O.3S–CO–180S–CO

18

Main circuit resistance

μ Ω

655

19

Mechanical endurance life

cycle

10000

 

 

Application Scenarios

 

product-630-250

product-630-250

 

Packing & Shipping

 
 

loading   package and shipping

 

FAQ

 

Q1: What is the rated voltage of this SF6 circuit breaker?

A: Its rated voltage is 126kV, suitable for 110kV power transmission and transformation systems.

Q2: What standards does your breaker comply with?

A: Designed and tested per IEC 62271-100, also meets GB 1984.

Q3: How long is the mechanical life?

A: Standard mechanical life: 10,000 times.

Q4: Do we need to refill SF6 gas frequently?

A: The gas leakage rate ≤0.5% per year. Under normal condition, no refilling is required within 10 years.

Q5: Is it indoor or outdoor type?

A: Most 126kV SF6 circuit breakers are outdoor type. Indoor tank type is customized for GIS room.

 

Hot Tags: lwl-126 outdoor high voltage ac sf6 circuit breaker, China lwl-126 outdoor high voltage ac sf6 circuit breaker manufacturers, suppliers, factory, 110kv sf6 circuit breaker, LWL 126 Outdoor High Voltage AC SF6 Circuit Breaker

Send Message