Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of lwl-126 outdoor high voltage ac sf6 circuit breaker in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium lwl-126 outdoor high voltage ac sf6 circuit breaker made in China here from our factory.
Product Description
LWL-126 outdoor high-voltage SF6 circuit breaker is suitable for AC 50Hz(60Hz)126kV power system, is the power system control and protection equipment, can also be used as a contact circuit breaker.
The circuit breaker meets the requirements of GB1984-2003 and IEC62271-100-2001. It uses SF6 gas as insulation and arc extinguishing medium, adopts self-energy arc extinguishing principle, and uses a new type spring operating mechanism, which has the characteristics of strong breaking ability, small operation power and high reliability.
Product Features
1.The circuit breaker adopts three-phase column type single-break structure,and is equipped with a spring-operated mechanism for three-phases, in centered arrangement, three phases linkage transmissed, so the appearance is novel and exquisite.
2. The circuit breaker adopts SF6 gas as insulation and arc extinguishing medium,and the three poles of the circuit breaker are with SF6gas connected during operation, and a pointer density relay is adopted to monitor its pressure and density.
3. Due to the use of self-energy arc extinguishing principle,and the circuit breaker movement system is with optimization design,so it effectively improves the mechanical efficiency,minimize the operating power;
4. The circuit breaker has excellent breaking performance and long electrical endurance life;and with high mechanical reliability and can be operated frequently;
5. The installation base frame and support are made of high-quality steel plate wholy bent,with all adopt hot-dip galvanizing process for the surface treatment.All exposed fasteners are made of high-strength materials and hot-dip galvanized,or use stainless steel spare parts.The outer housing of the mechanism cabinet is made of stainless steel, so the breaker is with excellent anti-corrosion performance;
6. Because of the inherent high insulation strength of SF6 gas,and the circuit breaker adopts the optimal contact movement,so the circuit breaker could break the capacitive current without re-strike;
7. High level of external insulation.The external insulation is in large creepage distance design,with creepage distance ratio≥31mm/kV, and with excellent anti-dirt performance. It could be safe operated in harsh environment;
8. Strong current-carrying capacity: if the breaker has temperature rise test at 1.2 times the rated current 3150A, which is in 3780A,the temperature rise at each point still has a large margin;
9. The overall appearance of the product is in compact structure,convenient for on-site installation and commissioning,and with small maintenance workload.
Product Show


LWL-126 SF6 Circuit Breaker Technical Specification
|
S.N. |
Name |
Unit |
Data |
||
|
1 |
Rated voltage |
kV |
126 |
||
|
2 |
Insulation Level |
1min power frequency withstand voltage (effective value,dry,wet types) |
Between factures |
kV |
230 |
|
Between poles or pole to earth |
kV |
230 |
|||
|
Lightening impulse withstand voltage(peak)(full wave1.2/50ps) |
Between factures |
kV |
550 |
||
|
Between poles or pole to earth |
kV |
550 |
|||
|
3 |
Rated frequency |
Hz |
50/60 |
||
|
4 |
Rated current |
A |
3150 |
||
|
5 |
Rated short circuit breaking current |
kA |
40 |
||
|
6 |
Rated short time withstand current |
kA |
40 |
||
|
7 |
Rated peak withstand current |
kA |
100 |
||
|
8 |
Rated short circuit endurance |
s |
3 |
||
|
9 |
Rated short circuit making current peak |
kA |
100 |
||
|
10 |
Short–line fault breaking current |
kA |
36/30 |
||
|
11 |
Rated cable line charging breaking current |
A |
31.5 |
||
|
12 |
Rated out–of–synchronism breaking current |
kA |
10 |
||
|
13 |
Total breaking operations at rated short circuit breaking current |
cycle |
20 |
||
|
14 |
First–pole–to–clear factor |
1.5 |
|||
|
15 |
SF6 gas pressure (20℃) |
Mpa |
0.5 |
||
|
16 |
Rated voltage of control and auxiliary circuits power |
DC220V DC110V |
|||
|
17 |
Rated operation sequence |
O–O.3S–CO–180S–CO |
|||
|
18 |
Main circuit resistance |
μ Ω |
655 |
||
|
19 |
Mechanical endurance life |
cycle |
10000 |
||
Application Scenarios


Packing & Shipping

FAQ
Q1: What is the rated voltage of this SF6 circuit breaker?
A: Its rated voltage is 126kV, suitable for 110kV power transmission and transformation systems.
Q2: What standards does your breaker comply with?
A: Designed and tested per IEC 62271-100, also meets GB 1984.
Q3: How long is the mechanical life?
A: Standard mechanical life: 10,000 times.
Q4: Do we need to refill SF6 gas frequently?
A: The gas leakage rate ≤0.5% per year. Under normal condition, no refilling is required within 10 years.
Q5: Is it indoor or outdoor type?
A: Most 126kV SF6 circuit breakers are outdoor type. Indoor tank type is customized for GIS room.