Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of lwl-40.5 outdoor high voltage ac sf6 circuit breaker in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium lwl-40.5 outdoor high voltage ac sf6 circuit breaker made in China here from our factory.
Product Description

Product Features
1.The LWL -40.5 type SF6 circuit breaker is in outdoor porcelain bushing column post structure, with spring-operated mechanism, and the mechanism and the breaker body is in "T" shape arrangement.
2.The whole breaker is with small size, light weight, simple structure, small operation power, and convenient in installation and commissioning.
3.Mechanical endurance life 10000 cycles, suitable for frequent operation;
4.Adopting air compressed type arc extinguishing chamber, with excellent breaking performance, and the electrical endurance life is up to 20 times;
5.Reliable sealing performance. The static sealing is using "O" sealing ring structure, and the dynamic sealing is using " √ " type sealing ring with spring pressure compensation structure. Ensure the annual gas leakage rate in 0.5%;
6.The secondary wiring terminal board of the transformer is produced by pressure injection technique, with strong anti-aging capability.
7.With internal or external installed current transformer, in which the metering level core adopts microcrystalline alloy high permeability performance material, and the accuracy is up to 0.2 or 0.2S levels. The breaker could be equipped with 2-4 current transformers per phase.
8.The installation base frame and support is made by whole steel plate rolling and use high-strength spare parts, with high mechanical reliability.
Ambient Conditions
- Ambient air temperature :-30ºC~+40ºC (special requirement: -40ºC~+40ºC);
- Altitude: not exceeding 3000m;
- Relative humidity: the daily average is not more than 95%, the monthly average is not more than 90%;
- Earthquake intensity: not exceeding 8 degrees;
- No fire, explosion, serious pollution, chemical corrosion and violent vibration.
LWL-40.5 Outdoor SF6 Circuit Breaker Main Technical Specification
|
S.N. |
Name |
Unit |
Data |
|
|
1 |
Rated voltage |
kV |
40.5 |
|
|
2 |
Rated current |
A |
630-2000 |
|
|
3 |
Rated insulation level |
Power frequency withstand voltage |
kV |
95 |
|
Lightning impulse withstand voltage |
kV |
185 |
||
|
4 |
Rated short circuit breaking current |
kA |
25/31.5 |
|
|
5 |
Rated out-of-synchronism breaking current |
kA |
7.9/10 |
|
|
6 |
Out of phase grounding fault breaking current |
kA |
27.4/34.8 |
|
|
7 |
Rated single capacitor bank breaking current |
A |
400 |
|
|
8 |
Rated operation sequence |
O–O.3s–CO–180s–CO |
||
|
9 |
Sf6 gas rated pressure |
Mpa |
0.45 |
|
|
10 |
Opening time (at rated voltage) |
ms |
30sts40 |
|
|
11 |
Closing time (at rated voltage) |
ms |
60sts80 |
|
|
12 |
Rated short circuit making current peak |
kA |
63/80 |
|
|
13 |
Rated short circuit endurance |
s |
4 |
|
|
14 |
Rated short time withstand current |
kA |
25/31.5 |
|
|
15 |
Rated peak withstand current |
kA |
63/80 |
|
|
16 |
Mechanical endurance life |
cycle |
10000 |
|
|
17 |
Rated short circuit breaking current 31.5kA/40kA total breaking operations |
cycle |
20 |
|
|
18 |
Rated current total breaking operations |
cycle |
2000 |
|
|
19 |
SF6 gas annual leakage |
% |
≤0.5 |
|
|
20 |
SF6 gas trace moisture content |
PPM |
≤150 |
|
|
21 |
Breaker external insulation leakage distance per unit withstand voltage |
mm/kV |
≥25,231 |
|
Circuit Breaker Ordering Information Required
1.Circuit breaker model, name, ordering quantity;
2.Rated voltage, rated current, rated short-circuit breaking current, distance between phases and also distance between upper and lower wiring outlet;
3.Rated voltage of energy charging motor and control voltage of mechanism;
4.Optional components solution;
5.The name and quantity of spare parts;
6.If the user has other special requirements (such as high altitude, extreme temperature and humidity etc.),it should be specified before ordering;
Packing & Shipping


Company Qualifications
Shaanxi Longxiang Electrical Co.,Ltd. holds dozens of national patents, including invention patents, utility model patents and design patents.

FAQ
Q1: What are key spare parts for VCB?
A: Vacuum interrupter, spring operating mechanism, solid-sealed pole, closing/tripping coil, charging motor, auxiliary switch, tulip contact, insulating pull rod, earthing switch, secondary terminal block etc.
Q2: What parameters are required for ordering VCB or complete switchgear?
A: Please provide rated voltage, rated current, short-circuit breaking current; operation mode (manual/motor); control coil voltage (AC/DC); indoor/outdoor; altitude & ambient temperature; special requirements such as solid-sealed pole, 5-proof interlock, communication function, OEM etc.
Q3: Do you provide technical support or installation guidance?
A: Yes, we provide comprehensive technical support, including detailed product documentation, installation guidance, and online assistance.
Q4: Do you support OEM & ODM customization?
A: Yes. Customization for enclosure color, parameters, nameplate, secondary drawing, IP class are available. English manuals, test reports and certificates can be supplied.
Q5: What is your terms of delivery?
A: EXW, FOB, CFR, CIF
Q6: What is your lead time?
A: 10-15working days for standard models; longer for non-standard customized orders.
Q7: What's the payment term?
A:We accept TT, 30% deposit and 70% before shipment, Western Union, L/C At Sight is ok!
Q8: What certificates do you have?
A:ISO9001,ISO14001,ISO45001,CE certificate and Type test report of product.