Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of vs1-12 vacuum circuit breaker in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium vs1-12 vacuum circuit breaker made in China here from our factory.
General Description
VS1-12 vacuum circuit breaker (also known as model ZN63A-12) is used for indoor 12kV switchgear, it is suitable to control and protect transmission and distribution system such as electric network equipment and industrial & mining industry etc as their protection and control unit.
Structural Characteristics
1.This series of vacuum circuit breaker is used integrated design for operating mechanism and VCB body with reasonable,beautiful and compact arrangement.
2.This series of VCB adopted vertical insulation house against impact due to different weather,it can effectively prevent VIS against damage by exterior factors.
3. With two kinds of installation: fixed type and withdrawable type. Both VCB types can meet different requirements for assembling between switchgear and breaker.
Applying Ambient Conditions
- Ambient temperature: -10℃ ~ +40℃
- The height above sea level: ≤1000m (besides the special requirements).
- Relative humidity: the average humidity of a day should be no more than 95%; the average humidity of a month should be no more than 90%
- Saturated vapor pressure: the average pressure of a day should be no more than 2.2kPa; the average pressure of a month should be no more than 1.8kPa
- Earthquake intensity: not exceed 8 degrees
It should be installed in the places without fire, explosion, serious filth, chemical erosion, and violent vibration.
VS1-12 Vacuum Circuit Breaker Main Technical Specifications
|
S.N. |
Name |
Unit |
Data |
|||||||
|
1 |
Rated voltage |
kV |
12 |
|||||||
|
2 |
Rated frequency |
Hz |
50 |
|||||||
|
3 |
Rated Insulation level |
1min power frequency withstand voltage |
kV |
42 |
||||||
|
Rated lightning impulse withstand voltage |
kV |
75 |
||||||||
|
4 |
Rated current |
A |
630 |
1250 |
1600 |
2000 |
2500 |
3150 |
4000* |
|
|
5 |
Rated short circuit breaking current Rated thermal stability current (effective value) |
kA |
20 |
20 |
||||||
|
25 |
25 |
25 |
||||||||
|
31.5 |
31.5 |
31.5 |
31.5 |
|||||||
|
40 |
40 |
40 |
40 |
40 |
40 |
|||||
|
50 |
||||||||||
|
6 |
Rated short circuit making current Dynamic stability rated current |
kA |
50 |
50 |
||||||
|
63 |
63 |
63 |
||||||||
|
80 |
80 |
80 |
80 |
|||||||
|
100 |
100 |
100 |
100 |
100 |
100 |
|||||
|
125 |
||||||||||
|
7 |
Breaking operations of rated short circuit breaking current |
cycle |
50,30 (above 40kA) |
|||||||
|
8 |
Rated short-circuit duration |
s |
4 |
|||||||
|
9 |
Rated operating sequence |
O-0.3s-CO-180s-CO/O-180s-CO-180s-CO(40kA and above) |
||||||||
|
10 |
Mechanical endurance |
cycle |
30000 |
|||||||
|
11* |
Rated breaking current of single capacitor bank |
A |
630 |
|||||||
|
12* |
Rated breaking current of back to back capacitor bank |
A |
400 |
|||||||
|
13 |
DC component |
50% |
||||||||
Note:
1. No.11 & 12 are provided when need.
2. Switchgear should with cold wind cooling when rated current is 4000A.
Mechanical Characteristic Parameters
|
S.N. |
Name |
Unit |
Data |
|
1 |
Clearance between open contacts |
mm |
11±1 |
|
2 |
Overtravel |
3.5±0.5 |
|
|
3 |
Contact bouncing duration at closing operation |
m/s |
≤ 2 |
| 4 |
Out of simultaneity of CO operations of three poles |
≤ 2 |
|
|
5 |
Opening Time |
≤ 50 |
|
|
6 |
Closing Time |
≤ 70 |
|
|
7 |
Average opening speed |
m/s |
0.9~1.3 |
|
8 |
Average closing speed |
0.4~0.8 |
Circuit Breaker Ordering Information Required
1.Circuit breaker model,name,ordering quantity;
2.Rated voltage,rated current,rated-short-circuit breaking current,distance between phases and also distance between upper and lower wiring outlet.
3.Rated voltage of energy charging motor and control voltage of mechanism;
4.Optional components solution;
5.The name and quantity of spare parts;
6.If the user has other special requirements(such as high altitude, extreme temperature and humidity etc.),it should be specified before ordering.
VS1-12 Vacuum Circuit Breaker Overall Outline Drawing



Transportation and Storage
1.When transport the vacuum circuit breaker, it should be packed and sealed into the packing box in whole set.
2.The packing, opening and storing all should be done in dry indoor condition.
3.During the transportation for VCB, it is not allowed to put it upside down and wetted by rain, and should not withstand strong vibration and bump.
4.The VCB should be kept in dry, ventilating, damp-proof and non-corrosive gas indoor conditions.
5. If it is for long time storing, the transmission part should be daubed with lubricating oil and check whether the ambient condition meets the requirements.
Packing & Shipping


Application Scenarios




FAQ
Q1: What are key spare parts for Vacuum circuit breaker?
A: Vacuum interrupter, spring operating mechanism, solidsealed pole, closing/tripping coil, charging motor, auxiliary switch, tulip contact, insulating pull rod, earthing switch, secondary terminal block.
Q2: Can you customize products according to our specifications?
A: Yes, we provide OEM & ODM services to meet your specific requirements.Customization for enclosure color, parameters, nameplate, secondary drawing, IP class are available. English manuals, test reports and certificates can be supplied.
Q3: What is the warranty period for your products?
A: We can offer a one-year warranty on all our products.
Q4: What's your best lead time for orders?
A: It depends on the quantity and customization requirements. Please feel free to contact us for more information.
Q5: Do you provide technical support?
A: Yes, we offer comprehensive technical support to our customers.
Q6: Do you inspect the finished products?
A: Yes, all products will be inspected strictly to ensure full compliance with ISO 9001 standards as well as relevant industry standards such as IEC. Also we will provide goods inspection reports for your reference before shipment.