ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker

ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker

1.Rated voltage: 12kV
2.Rated frequency: 50/60Hz
3.Rated Current: 630/1250A
4.Rated short-circuit breaking current: 20/25kA
5.Operating mechanism type: Specialized mechanism by manual&electrical
6.The air filthy should be within III degree.
7.Features: small volume, light weight, anti-condensation, free maintenance
Send Inquiry
Description
Technical Parameters

Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of zw32-12 outdoor high voltage vacuum circuit breaker in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium zw32-12 outdoor high voltage vacuum circuit breaker made in China here from our factory.

 

General Description

 

ZW32-12 outdoor high voltage vacuum circuit breaker is three-phase AC,50(60) Hz outdoor power distribution equipment with the rated voltage of 12kV. It is mainly used to break and close the load current and short circuit current in the electric power system.

 

It fits to be used to protect and control the circuit in substation, mining and industrial enterprises. It also can be used in the frequently operation places such as the rural power network. The product is accordance with GB1984-2003 standard.

 

Product Features

 

The circuit breaker has the characteristics of small volume, light weight,
anti-condensation, free maintenance and so on. It can adapt to the harsh weather conditions and dirty environment.

 

The ZW32-12 VCB isolating switch combination consists of vacuum circuit breaker body and isolating switch.

product-842-605

 

Use of Enviromental Conditions

 

1.Ambient temperature: -30℃ to +40℃;
2.The height above sea level: ≤1000m; (besides the special requirements);
3.Relative humidity: the average humidity of a day should be no more than 95%; the average humidity of a month should be no more than 90%;
4.Saturated vapor pressure: the average pressure of a day should be no more than 2.2kPa,the average pressure of a month should be no more than 1.8kPa.
5.Earthquake intensity: not exceed 8 degrees.
6.Wind pressure: no more than 700pa (it is equivalent to wind speed of 34 m/s).
7.The air filthy should be within III degree.
8.It should be used in the places without fire, explosion, serious filth, chemical erosion and violent vibration.

 

Main Technical Specification

 

S.N.

Name

Unit

Data

1

Rated voltage

kV

12

2

Rated frequency

Hz

50/60

3

Rated current

A

630

4

Rated short circuit breaking current

kA

20

5

Rated short circuit making current

kA

50

6

Rated peak withstand current

kA

50

7

Rated short time withstand current

kA

20

8

Rated short–circuit duration

s

4

9

Rated power frequency withstand voltage

Dry

kV

42/1min

Wet

kV

34/1min

10

Rated lightning impulse withstand voltage

Between phases. phase to ground

kV

75

Between gaps

kV

85

11

Rated operating sequence

 

O–0.3s–CO–180s–CO

12

Breaking operations of short circuit current

cycle

ClassE2(50cycles)

13

Mechanical endurance

cycle

(classM1 ) 10000

14

Operating mechanism type

 

Specialized mechanism(by manual,electrical)

15

Clearance between open contacts

mm

9 ± 1

16

Contact stroke of contacts

mm

2 ± 0.5

17

Simultaneity of CO operations of three poles

ms

≤2

18

Contact bouncing duration at closing operation

ms

≤2

19

Closing time

ms

30~60

20

Opening time

ms

20~40

21

Average closing speed

m/s

0.4~0.8

22

Average opening speed

m/s

1.0~1.4

23

Main circuit resistance of each pole

μ Ω

≤80

24

DC component

50%(Max.)

 

ZW32-12 Circuit Breaker Ordering Information Required

 

1. Circuit breaker model, name, ordering quantity;
2. Rated voltage, rated current, rated short-circuit breaking current, distance between phases and also distance between upper and lower wiring outlet;
3. Rated voltage of energy charging motor and control voltage of mechanism;
4. Optional components solution
5. The name and quantity of spare parts;
6. If the user has other special requirements (such as high altitude, extreme temperature and humidity etc.), it should be specified before ordering;

 

Overall Outline Drawing

 

product-666-478

 

Application Scenarios

 

product-924-542

product-938-542

10kV overhead urban & rural distribution network

 

 

Company Qualifications

 

Shaanxi Longxiang Electrical Co.,Ltd. holds dozens of national patents, including invention patents, utility model patents and design patents.

product-1357-705

 

FAQ

 

Q: Can the installation type be customized?

A: Yes, the installation type can be customized to Fixed or Withdrawable

Q: What is the minimum order quantity?

A: MOQ is 1 set.

Q:What are key spare parts for VCB?

A: Vacuum interrupter, spring operating mechanism, solid-sealed pole, closing/tripping coil, charging motor, auxiliary switch, tulip contact, insulating pull rod, earthing switch, secondary terminal block etc.

Q: Do you support OEM & ODM customization?

A: Yes. Customization for enclosure color, parameters, nameplate, secondary drawing, IP class are available. English manuals, test reports and certificates can be supplied.

Q: What are the available payment terms?

A: T/T and L/C are acceptable , TT will be more appreciated. 30% T/T in advance and 70% balance before shipment.

Q: Do you have relevant test certificates?

A: We can provide type test reports, also the third-party inspection before delivery if required.

 

Send Message