The electrical five-preventions refer to the collective term for the five types of misoperation-prevention functions that electrical equipment (high-voltage switchgear) should have to ensure the safety of personnel and equipment. They are one of the important measures for power safety.
01 What are the electrical "Five-Preventions"?
According to the "Safety Management Regulations of the State Grid Corporation of China for Preventing Electrical Misoperations," the specific contents of the electrical five preventions are as follows:
1. Prevent opening and closing disconnectors under load.
When the circuit breaker, load switch, or contactor is in the closed state, the disconnector must not be operated.
2. Prevent mistaken opening and mistaken closing of circuit breakers, load switches, and contactors.
Only when the operating instruction corresponds to the operating equipment may the operated equipment be operated.
3. Prevent closing the circuit breaker or load switch when the grounding switch is in the closed position.
Only when the grounding switch is in the open state may the disconnector be closed or the handcart be moved to the working position, and only then may the circuit breaker or load switch be closed.
4. Prevent mistaken closing of the grounding switch while energized.
Only when the circuit breaker is in the open state may the disconnector be operated or the handcart be moved from the working position to the test position, and only then may the grounding switch be closed.
5. Prevent mistaken entry into an energized compartment.
Only when the compartment is not energized may the door be opened to enter the compartment.
For the "five preventions" functions of electrical equipment misoperation-prevention devices, except for "preventing mistaken opening and mistaken closing of circuit breakers," which at the present stage may adopt advisory measures due to technical reasons, the other four protection functions must adopt mandatory measures to prevent electrical misoperations.

02 How are the "Five Protections" realized?
1. Prevent mistaken entry into an energized compartment
After the working handcart is cranked to the "isolation/test" position, the grounded metal partition automatically drops down to cover the energized stationary contact part, preventing personnel entering the switchgear cabinet for maintenance from contacting energized parts. Only after the switch grounding blade is closed is the mechanical interlock of the rear cabinet door allowed to open the cabinet door.
2. Prevent opening and closing of primary and secondary contacts under load
When the contactor is in the closed state, the mechanical interlock baffle interlocked with the contactor pushes the connecting rod on the propulsion mechanism, making the screw of the propulsion mechanism unable to rotate. Through this design, when under load, the primary and secondary contacts cannot be opened or closed.
3.Prevent hanging grounding wires while energized
When the handcart enters the working position, the baffle of the propulsion mechanism presses against the curtain plate device of the grounding switch closing mechanism, so that the curtain plate cannot be opened and the grounding switch cannot be closed.
4.Prevent closing while a grounding wire is connected
When the grounding blade is closed, the baffle of the curtain plate device will obstruct the handcart from entering the cabinet, thereby avoiding the possibility of closing the contactor in the grounded state.
5.Prevent mistaken opening and mistaken closing of circuit breakers
Operating personnel should always keep the regulations firmly in mind and operate according to the operation ticket.
The realization of the electrical "five preventions" functions has become one of the important measures for safe production in electric power. With the continuous development of the power grid and the continuous updating of technology, misoperation-prevention devices are continuously improved and perfected.
03 Conventional misoperation-prevention locking devices
The design principle of misoperation-prevention devices is: for all high-voltage electrical equipment that may cause misoperations, misoperation-prevention devices and corresponding misoperation-prevention electrical locking circuits should be installed. There are four main conventional misoperation-prevention locking methods: mechanical locking, program locks, electrical interlocks, and electromagnetic locks.
1.Mechanical locking
This uses mechanical mechanisms of mutual restriction and linkage between the operating parts of switchgear cabinets or outdoor disconnectors to achieve the locking requirements for sequential actions. During operation, mechanical locking requires no auxiliary operations such as keys, and can automatically unlock step by step as the operating sequence proceeds correctly. In the event of a misoperation, automatic locking can be achieved to prevent the misoperation from proceeding. Mechanical locking can achieve both forward and reverse locking requirements, and has the advantages of intuitive locking, being not easily damaged, low maintenance workload, and convenient operation.
However, mechanical locking can only be applied between the mechanical action-related parts inside switchgear cabinets and outdoor disconnectors, and cannot realize the connection with the actions of electrical components. It is also powerless for locking requirements between two cabinets, between a switchgear cabinet and outdoor distribution equipment, and between an outdoor disconnector and a switch (or other disconnector). Therefore, in switchgear cabinets and outdoor disconnectors, mechanical locking can only be the main method, and other locking methods must also be supplemented to meet all five protection requirements.
2.Program locks (or mechanical program locks)
These use keys transmitted or exchanged according to the operating program to achieve the requirements for sequential unlocking operations. Their greatest advantage is that key transmission is not limited by distance, so they are widely used. During operation, program locks involve auxiliary actions such as key transmission and changes in the number of keys, which conform to the requirements of the operating sequence specified in the operation ticket for unlocking conditions and are completely consistent with the walking route specified in the operation ticket, so they are also easily accepted by operating personnel.
3.Electrical locking
This achieves unlocking operation through the electromagnetic mechanism action of electromagnetic coils, and is an indispensable locking element in the locking link for preventing mistaken entry into energized compartments. The advantages of electrical locking are convenient operation and no auxiliary actions, but the following prominent problems also exist in installation and use:
① Generally speaking, when an electromagnetic lock is used alone, it only has an unlocking function and no reverse locking function. It must be used in combination with an electrical interlock circuit to have forward and reverse locking functions;
② As a locking element, the electromagnetic lock has a complex structure. The electromagnetic coil is prone to moisture and mildew damage outdoors, reducing insulation performance and increasing the failure rate of the DC system;
③ Cables need to be laid, increasing additional construction work;
④ Auxiliary contacts of the operating mechanism need to be connected in series. According to operating experience, auxiliary contacts are prone to poor contact, which affects the reliability of operation;
⑤ On the control switch of the circuit breaker, locking measures are generally lacking.
4.Microcomputer misoperation-prevention locking devices
Since the early 1990s, microcomputer technology has entered the field of misoperation-prevention locking. A microcomputer misoperation-prevention locking device is a device that uses computer technology and is used for preventing electrical misoperations in high-voltage switchgear. After more than 10 years of development, microcomputer misoperation-prevention locking devices have gradually matured and have been widely promoted in power systems. Through software, microcomputer five-prevention systems turn a large number of secondary locking circuits on site into a five-prevention locking rule base in the computer, realizing the digitalization of misoperation-prevention locking and enabling misoperation-prevention functions that previously could not be realized or were difficult to realize. This should be said to be a leap in misoperation-prevention locking technology for electrical equipment.
These locking methods have played a positive role in misoperation-prevention work, and practice has proved that the advantages and disadvantages of various traditional locking methods have been fully demonstrated. After nearly ten years of development, microcomputer misoperation-prevention locking devices have been accepted by the vast number of users in the power system. In substations of 110 kV and above, microcomputer five-prevention has become the mainstream product of misoperation-prevention locking. The number of manufacturers producing microcomputer five-prevention products is also constantly increasing, and there are more and more types of products.