Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of epoxy resin embedded pole in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium epoxy resin embedded pole made in China here from our factory.
Products Description

Epoxy resin embedded pole embeds the conductive parts related to the vacuum arcing chamber and circuit breaker into the epoxy resin, which is a kind of solid insulation material that is easy to cure. Epoxy resin is poured on the outside for encapsulation, and the pole column is sealed to form an integral part of the whole circuit breaker pole column. Epoxy resin is not only the primary part of the main insulation, but also its mechanical support. Its electric field distribution is better than various forms of insulation diaphragm structure.
Main Technical Date
| Main Technical Data | ||||
| Rated voltage | kv | 40.5 | ||
| Rated current | A | 1600/2000 | ||
| Rated frequency | Hz | 50 | ||
| Rated short-circuit breaking current | KA | 31.5 | ||
| operations of short-circuit making current interruption | times | 30 | ||
| Rated short-circuit making current | KA | 80 | ||
| Rated short-time withstand and current(4S) | KA | 31.5 | ||
| Rated single capacitor bank breaking current | A | 630 | ||
| Rated back-to-back capacitor bank breaking current | A | 400 | ||
| Short-time(1min) power-frequency withstand voltage | KA | 95 | ||
| Rated lightning impulse withstand voltage (peak) | kA | 185 | ||
| Circuit resistance at rate contact force | μΩ | ≤20 | ||
| Mechanical life | times | 10000 | ||
| Contact closing force due to bellows and atmosphere | N | 250±50 | ||
| Counterforce at rated contact force | N | 350±50 | ||
| Contact erosion limit | mm | 3 | ||
| Shelf life | years | 20 | ||
| Part discharge | pc | ≤5 | ||
| Rated operating sequence | 0-0.3-CO-180s -CO | |||
| MECHANICAL DATE OF CIRCUIT-BREAKING EQUIPPED WITN THE INTERRUPTERS | ||||
| Rated contact stroke | mm | 18±1 | ||
| Contact connection stroke | mm | 4±1 | ||
| Average opening speed | m/s | 1.6±0.2 | ||
| Average closing speed | m/s | 0.8±0.3 | ||
| Added contact force | N | 3150±200 | ||
| Bounce duration of contact closing | ms | ≤2 | ||
| Out of simultaneity of contact closing and opening | ms | ≤1 | ||
| Max. overtravel | mm | ≤2 | ||
Outline Drawing

Difference Between Embedded Pole and Traditional Insulating Cylinder
|
Comparison Item |
Embedded Pole |
Traditional Insulating Cylinder |
|
Structure |
Modular design with simple structure and few detachable parts; the vacuum interrupter is encapsulated inside solid insulating material |
The insulating shell of the vacuum interrupter is exposed to the air with a large number of components |
|
Insulation Mode |
Convert surface insulation into volume insulation for higher insulation capacity |
Rely on surface insulation of the interrupter shell, vulnerable to external environmental impacts |
|
Conductor Overlap & Fasteners |
Conductor overlapping surfaces reduced from 6 groups to 3 groups; connecting bolts cut from 8 to 1–3, fewer connection points |
More conductor overlapping surfaces and connecting bolts, numerous connection joints |
|
Installation Feature |
Easy to install with high reliability |
More components and complicated installation procedures |
|
Miniaturization |
More favorable for miniaturized design of vacuum circuit breakers and switchgear |
The shell requires sufficient length to guarantee insulation, which hinders equipment miniaturization |
|
Environmental Resistance |
Isolated by solid material, minimizing the impact of dust, moisture and other external factors; strong environmental adaptability |
Exposed shell is prone to contamination by dust and humidity, impairing performance and reliability |
|
Maintenance |
Completely maintenance-free throughout the product service life |
Exposed structure easily accumulates dirt and requires regular inspection and maintenance |
|
Application Scenarios |
Harsh working conditions such as chemical industry, metallurgy and mining |
Conventional power distribution sites with favorable ambient conditions |
Application of Epoxy Resin Embedded Pole
1.Intended for indoor distribution equipment of three-phase AC distribution systems.
2.Provide protection and control for electrical equipment in industrial and mining enterprises, power plants and substations.
3.Preferred solution for sites with requirements of oil-free design, low maintenance and frequent switching.
4.Installed in mid-mounted switchgear, double-deck switchgear and fixed switchgear for the control and protection of high-voltage electrical equipment.

Honor and qualification
Official certification, professional after sales service.

CE

ISO9001

ISO14001

ISO45001

Invention patent