Shaanxi Longxiang Electrical Co., Ltd. is one of the most reliable manufacturers and suppliers of 12kv 630a indoor vcb in China. With abundant experience, we are committed to providing high quality customized products with competitive price. Welcome to buy premium 12kv 630a indoor vcb made in China here from our factory.
General Description
VCB stands for Vacuum Circuit Breaker,12kV Indoor Vacuum Circuit Breaker is a three-phase AC 50Hz medium-voltage switching device, designed for indoor power distribution systems at rated voltage 12kV. It adopts vacuum arc-extinguishing technology, serving as core control and protection equipment for substations, industrial plants and commercial power networks. According to the different installation forms in switchgear, it can be fixed type or handcart type. Withdrawable type is widely matched with KYN28A-12 and the fixed type is applicable to XGN series.


Operating Conditions
Ambient temperature: -10℃ ~ +40℃
Altitude: ≤1000m; reinforced insulation customization available for high altitude
Seismic resistance ≤8°,
Humidity: Daily average ≤95%, monthly average ≤90%
Indoor installation, free of flammable, corrosive gas and severe vibration
Core Design and Structure
This 12kV indoor VCB features modular design with epoxy resin solid-sealed poles by APG process. The solid-sealed structure isolates vacuum interrupters from dust, moisture and contamination, delivering stable insulation performance. The integrated spring energy-storage operating mechanism supports both manual and electric closing & opening. Mechanical and electrical interlock devices are equipped to block misoperation and ensure operator safety. Compact layout saves cabinet space and simplifies on-site assembly and replacement.
Operating Principle
The VCB uses the cup shape axial magnetic field which has the extremely high vacuum degree.When the moved and fixed contacts open with electricity under the action of operating mechanism, the vacuum can be produced between contacts. Because of the declining slot on the moving and fixing contact,when the arc current flow them, it will produce bigger circle component and form axial magnetic field between contacts. It can make are keep the diffuse form, the are burns on the surface of the contacts uniformly and keep lower are voltage. When the current is reach zero naturally, the ion, electron and metal vapor remained can accumulated or composed in the surface of contacts or shield cover within few microseconds. The dialectic insulation strength on the gap of vacuum interrupter will recovery rapidly, the are is quenched and realize the breaking purpose. Because it was adopted advanced axial magnetic technology, the vacuum interrupter has strong and stable breaking current capability.
Technical Parameters for VS1 12kV Indoor VCB
|
S.N |
Name |
Unit |
Data |
|||||||
|
1 |
Rated voltage |
kV |
12 |
|||||||
|
2 |
Rated frequency |
Hz |
50 |
|||||||
|
3 |
Rated Insulation level |
1min power frequency withstand voltage |
kV |
42 |
||||||
|
Rated lightning impulse withstand voltage |
kV |
75 |
||||||||
|
4 |
Rated current |
A |
630 |
1250 |
1600 |
2000 |
2500 |
3150 |
4000* |
|
|
5 |
Rated short circuit breaking current Rated thermal stability current (effective value) |
kA |
20 |
20 |
||||||
|
25 |
25 |
25 |
||||||||
|
31.5 |
31.5 |
31.5 |
31.5 |
|||||||
|
40 |
40 |
40 |
40 |
40 |
40 |
|||||
|
50 |
||||||||||
|
6 |
Rated short circuit making current Dynamic stability rated current |
kA |
50 |
50 |
||||||
|
63 |
63 |
63 |
||||||||
|
80 |
80 |
80 |
80 |
|||||||
|
100 |
100 |
100 |
100 |
100 |
100 |
|||||
|
125 |
||||||||||
|
7 |
Breaking operations of rated short circuit breaking current |
cycle |
50,30 (above 40kA) |
|||||||
|
8 |
Rated short-circuit duration |
s |
4 |
|||||||
|
9 |
Rated operating sequence |
O-0.3s-CO-180s-CO/O-180s-CO-180s-CO(40kA and above) |
||||||||
|
10 |
Mechanical endurance |
cycle |
30000 |
|||||||
|
11* |
Rated breaking current of single capacitor bank |
A |
630 |
|||||||
|
12* |
Rated breaking current of back to back capacitor bank |
A |
400 |
|||||||
|
13 |
DC component |
50% |
||||||||
1. No.11 & 12 are provided when need.
2. Switchgear should with cold wind cooling when rated current is 4000A.
Key Performance Advantages of 12KV Indoor VCB
Superior Interruption Performance
Adopts sealed vacuum interrupter for ultra-fast arc quenching at current zero, rapid dielectric recovery, low re-ignition risk. Stable short-circuit breaking capacity up to 40kA, suitable for frequent switching operations and repetitive fault clearance.
Low Maintenance & Long Service Life
Hermetically sealed vacuum interrupter is maintenance-free during normal service. Spring energy-storage mechanism delivers long mechanical life (10,000–30,000 operations). Solid-sealed epoxy pole resists dust, moisture and condensation.
Compact Modular Structure
Small footprint and light weight. Available in withdrawable handcart type and fixed type, perfectly compatible with KYN28A-12 and mainstream 12kV switchgears. Standard dimensions ensure interchangeability and easy cabinet integration.
Multiple Operation Options
Support both manual and electric closing / opening. Match various control power supply (AC/DC), satisfy different substation and industrial control schemes.
12kV Indoor VCB, VS1-12 Vacuum Circuit Breaker with XIHARI Type Test Report

fAQ
Q:1.What is 12kV Indoor VCB?
A:12kV Indoor Vacuum Circuit Breaker (VS1/ZN63A-12) is an indoor medium-voltage switching and protection device for 50/60Hz three-phase AC power systems. It adopts vacuum interrupter for arc extinction, widely used inside KYN28A-12 switchgears.
Q:2.Can this 12kV VCB work on 10kV / 11kV power grid?
A:Yes. 12kV refers to the equipment's highest rated voltage; it is the standard model for 10kV (Chinese standard) and 11kV (IEC) nominal distribution systems.
Q:3.What is the difference between withdrawable handcart type and fixed type?
A:The withdrawable handcart VCB can be racked between working, test and isolated positions, convenient for maintenance and replacement without bus power cut, matching KYN28A-12. Fixed VCB is bolted inside switchgear, simpler structure and lower cost, suitable for XGN fixed switchgear.
Q:4.What standard does your VCB follow?
A:IEC 62271-100, GB/T 1984.
Q:5.Can it be used outdoors?
A:No. Standard 12kV indoor VCB is only designed for indoor environment. For outdoor application, please select ZW series outdoor VCB.
Q:6.What is the warranty term?
A:24 months from delivery date against manufacturing defects. Damage caused by improper installation, operation or modification is excluded.